TDS ions from dissolved solids create the ability for water to conduct an electrical current, which is measured by the IC Controls 210-C(TDS) analyzer and immediately displayed as sodium chloride ppm or mg/L, or as a conductivity analyzer displayed as µS/cm. When directly measured in process the conductivity detected is not neutralized. IC Controls 210-C(TDS) analyzer has an adjustable SCF solids content factor to match your application.
Typical non neutralized TDS solids content factors:
TDS as NaCl: 0.47 to 0.50
TDS as 442®: 0.65 to 0.85
TDS as KCl: 0.50 to 0.57
Learn more:
- Blog – Meeting Environmental Standards for TDS in Wastewater Treatment
- Technical Article – Total Dissolved Solids Measurement
